Technical Data of MX+OF Shunt Trip and Auxiliary Switches
Category Number |
27109 |
27110 |
27118 |
||||||||
Nominal Line Voltage, V | 120 | 240 | 277 | 110 | 125 | 48 | 48 | 12 | 24 | 24 | |
10% to 20% |
Alternative Current | ■ | ■ | ■ | - | - | ■ | - | - | ■ | - |
Direct Current | - | - | - | ■ | ■ | - | ■ | ■ | - | ■ | |
Operating Frequency, 50/60Hz |
■ | ■ | ■ | - | - | ■ | - | - | ■ | - | |
Minimum Cut-out Voltage, V |
60.5 | 60.5 | 60.5 | 60.5 | 60.5 | 26.4 | 26.4 | 6.6 | 6.6 | 6.6 | |
Inrush Current, A |
0.4 | 0.8 | 1 | 0.3 | 0.3 | 1 | 0.7 | 2.5 | 7.7 | 5.6 | |
Inrush Power, VA |
44 | 184 | 277 | 38 | 45 | 48 | 33.6 | 30 | 185 | 135 | |
Minimum Control Impulse Duration, ms |
8 |
8 |
8 |
||||||||
Power Circuit Breaking Time, ms |
18 |
18 |
18 |