Selection table and technical data of EZC series MCCBs, Easypact Type
Easypact circuit breakers |
EZC100N |
EZC250N |
EZC400N |
||
Fixed version |
■ |
■ |
■ |
||
Plug-in version |
- |
- |
- |
||
Rated current, A |
In |
At 40℃ |
63, 80, 100 |
160, 200, 250 |
300, 350, 400 |
Rated insulation voltage |
Ui |
|
690V |
||
Rated impulse voltage |
Uimp |
|
6kV |
||
Rated operational voltage |
Ue |
AC50/60Hz |
415V |
550V |
550V |
DC |
125V |
250V |
250V |
||
Electrical characteristics as per IEC 60947-2 |
|||||
Ultimate breaking capacity, Icu |
AC50/60Hz |
110/130V |
25kA |
50kA |
85kA |
220/230/240V |
18kA |
50kA |
36kA |
||
380V |
2.5kA |
25kA |
36kA |
||
400/415V |
2.5kA |
20kA |
36kA |
||
550V |
- |
8 |
15kA |
||
Rated service breaking capacity, Ics |
%Icu |
110-400V |
50% |
50% |
50% |
415-550V |
50% |
50% |
50% |
||
Suitability for isolation |
|
|
■ |
■ |
■ |
Utilization category |
|
|
A |
A |
A |
Pollution degree |
|
|
3 |
3 |
3 |
Endurance, C-O cycles |
Mechanical |
8500 |
10000 |
4000 |
|
Electrical |
1500 |
5000 |
1000 |
Send Inquiry
If you have any enquiry about quotation or cooperation,please feel free to email us at teatonele@yahoo.com or use the following enquiry form. Our sales representative will contact you within 24 hours. Thank you for your interest in our products.