Selection table and technical data of NSX series MCCBs, Compact Type
Compact circuit breakers, NSX |
100N |
160N |
250N |
400N |
630N |
||
Rated insulation voltage |
Ui |
800V |
|||||
Rated operational voltage |
Ue |
AC50/60Hz |
690V |
||||
Rated impulse voltage |
Uimp |
8kV |
|||||
Suitability for isolation |
IEC 60947-2 |
■ |
■ |
■ |
■ |
■ |
|
Number of poles |
3, 4 |
3, 4 |
3, 4 |
3 |
3 |
||
Utilization category |
A |
||||||
Pollution degree |
IEC 60664-1 |
3 |
|||||
Control |
Manual |
With toggle |
■ |
■ |
■ |
■ |
■ |
With direct handle |
■ |
■ |
■ |
■ |
■ |
||
Electrical |
With remote control |
■ |
■ |
■ |
■ |
■ |
|
Versions |
Fixed |
■ |
■ |
■ |
■ |
■ |
|
Withdraw |
Plug-in base |
■ |
■ |
■ |
■ |
■ |
|
Chassis |
■ |
■ |
■ |
■ |
■ |
||
Electrical characteristics as per IEC 60947-2 |
|||||||
Rated current, A |
In |
At 40℃ |
100 |
160 |
250 |
400 |
630 |
Ultimate breaking capacity, Icu, kA |
AC50/60Hz |
220/240V |
90 |
90 |
90 |
85 |
85 |
380/415V |
50 |
50 |
50 |
50 |
50 |
||
440V |
50 |
50 |
50 |
42 |
42 |
||
500V |
36 |
36 |
36 |
30 |
30 |
||
525V |
35 |
35 |
35 |
22 |
22 |
||
660/690V |
10 |
10 |
10 |
10 |
10 |
||
Rated service breaking capacity, Ics, kA |
220/240V |
90 |
90 |
90 |
85 |
85 |
|
380/415V |
50 |
50 |
50 |
50 |
50 |
||
440V |
50 |
50 |
50 |
42 |
42 |
||
500V |
36 |
36 |
36 |
30 |
30 |
||
525V |
35 |
35 |
35 |
11 |
11 |
||
660/690V |
10 |
10 |
10 |
10 |
10 |
||
Endurance, C-O cycles |
Mechanical, x1000 |
50 |
40 |
20 |
15 |
15 |
|
Electrical |
440V, x1000 |
30 |
20 |
10 |
6 |
4 |
|
690V, x1000 |
10 |
7.5 |
5 |
3 |
2 |